Schwimmerventile

Know-How Float Valves

Apploication

 

Level controllers and float valves control the liquid level in a vessel or tank.

Level controller or float valve


float valve NV 66e You should use a level controller with float chamber if the float cannot be mounted in the vessel. It is mounted in the pipeline and connected to the vessel by means of balancing lines. Float valves have no float chamber. The float is always mounted in the vessel.

Feed and drain valves


Feed valves (code letter "Z") close as the float rises and prevent overflowing. Drain valves (code letter "A") close as the float sinks and ensure that the liquid level does not drop below the required level.

Mounting of float-controlled valves


- Float valves for installations in vessels are mounted inside the vessel complete with float.
- Float valves for installation on vessels are flange- mounted on the outer skin of the vessel.
- Float valves for installation in pipe lines are installed in the feed/drain pipe.
The float lever either projects into the vessel or the float movemen´s is transferred by means of a cable.

float valves - installation in tanks or vessels float valves - installation at tanks or vessels float valves - installation in pipelines
valves for installation in vessels valves for installation at tanks valves for installation in pipelines

 

Flow direction of float valves


The flow direction determines the mounting arrangement and type of float lever used:
- horizontal, flow direction towards or away from the vessel code letter "w"
- vertical, flow direction upwards code letter "o")
- vertical, flow direction downwards (code letter "u")

Selecting valve type and nominal diameter


To select the valve type and determine the required nominal diameter you should calculate first the operating performance parameter Kv based on the maximum operating values and minimum pressure drop Δp. You should choose a valve having a Kvs value which is 30 % greater than the calculated Kv figure.
grafic possble pressure range for bleeding and venting valves

 

Selecting the operating pressure range


The maximum operating pressure of your system must be within the operating pressure range of the valve; if not, the float valve will not close or open.

Pressure inside the vessel


Check whether the vessel in which the float is to be mounted is not pressurised. If the vessel is pressurised a pressure-resistant ball float has to be fitted. Cylindrical floats may only be used in non-pressurised vessels.

Temperature


If the valve is to be used for temperatures above 80 °C or a liquid other than water, the compatibility of the elastomers must be checked. For hydrocarbons like gasoline, petrol etc., for example, the valves are fitted with FPM elastomers, whilst for higher temperatures they are fitted with EPDM or, if necessary, with a metallic cone seal.

Adapting the float


Float valves are normally designed for media with the specific gravity of water. By choosing a different float geometry, by filling the float or by altering the operating pressure range, we can adapt the floats to other media.

Balance and double seat


Single seat non-balanced float valves are used for low pressures. They are relatively insensitive to contamination and dirt deposits.
Single seat balanced valves can be used for larger pressure drops and feature smaller floats.
Double seat valves are specially suitable for large flow rates.
overfill protection NV 36SF

 

Overflow preventers


A special product are the PTB-approved overflow preventers Types 36S and 36SF. These are mechanical safety devices for flammable liquids.

Seat leakage


Level controllers and float valves are control valves which are not required to provide a leak-proof seal (VDI/VDE Guideline 2174). For leakproof shutoff, shut-off valves must be used. Normally our valves leave the factory with perfectly leakproof valve seats. During operation, however, solid particles (e.g. sand, welding nuggets etc.) often cause damage and seat leakage. Any low leakage requirement must be expressly specified when ordering. Valve leakage can be considerably reduced by special measures such as lapping the valve seat, using special cone seals and increasing the valve closing force by changing the lever geometry or increasing the size of the float.

Adjustable filling level


In the case of valves fitted with float rod and adjustable float, the level in the vessel can be adjusted by sliding the float along the rod.

 

float valves - parallel guide

Float rod guide

 

For float rods a guide must be provided in the vessel to prevent the float oscillating. Float valves with parallel guide or special designs featuring a top-mounted float do not require a rod guide.

Operation


Make sure that no pressure surges or water hammer occur in the system, which could destroy the float. In the case of foaming media and the resulting reduction of the specific gravity, a float valve cannot operate reliably. In this case a foam abatement circuit should be provided.

Maintenance


Float valves and level controllers should be cleaned and serviced at regular intervals. This rule applies especially to valves which are rarely operated e.g. valves fitted in sprinkler systems.
Thorough cleaning is important in the case of liquids containing substances which easily form deposits (such as iron, lime, suspended solids etc). Sand and abrasive particles carried along in the liquid can cause rapid wear. Please ask for specially adapted valves.

Valves free of oil and grease or silicone


Please pay attention to order an fit only spares free of oil and grease resp. free of silicone.

Please consult our engineer if extreme operating conditions apply or whenever you are in doubt.

Notes on Safety, operarting instruction etc. MUST be followed.

 